K573HB-2P 35-35 special Bitzer condenser seawater-resistant
Bitzer K573HB-2P 35/35 special water-cooled condensing unit
for refrigeration
Suitable for standard refrigerants, including. HFOs, R290 and R1270.
Shell and Tube condenser with finned tubes and shielding gas filling.
Maximum working pressure is 33 bar.
mounting brackets on the bottom and on the top front
seawater resistant versionSuitable
EXPERT ADVICE
Professionals in refrigeration technology
SINCE 1986
Since 1986 in refrigeration technology
FACTORY GUARANTEE
You have Always genuine manufacturer's warranty
CUSTOMER SERVICE
info@mfmref.com
K573HB-2P 35/35 special Bitzer water-cooled condensing unit
for refrigeration
Seawater-resistant implementation: connection male thread
Suitable for standard refrigerants.
Shell and Tube condenser with finned pipes, protective gas charge, entrance.
Rotalock or soldering connection soldering connection, flange with fluid output.
Rotalock valve with solder connection, K123HB.. K4803TB with second fluid output (ships), right angle mounting brackets above and below.
Bitzer K573HB is Suitable for all commonly used refrigerants (HFC, HFO, HFC/HFO blends) and including a version approved for use with hydrocarbons (propane, propylene),
K573HB Bitzer condensers represent a standard and robust solution for seawater cooled applications.
These condenser K573HB ensure excellent reliability thanks to the unique tube-brazing process and the coating of the tube sheets.
While the use of a low-fouling design for the exchange tubes means that the K573HB condenser can deliver a consistent performance throughout its life.
The Bitzer Sea water cooled condensers have resistant design for seawater. They are proven over decades in all maritime applications.
The condensers are extremely corrosion-resistant to seawater. The low fouling profile tubes and the coating of tube sheets and coolant reversing covers make them the first choice.
- Technical Data
- Weight 63 kg
- Total width 1213 mm
- Total height 377 mm
- Jacket tube diameter 216 mm
- Refrigerant inlet 35 mm - 1 3/8''
- Refrigerant outlet 28 mm - 1 1/8''
- Alternative refrigerant outlet 1 3/4'' - 12 UNF
- Coolant inlet (2 passes) 2''
- Coolant outlet (2 passes) 2''
- Coolant inlet (4 passes) 1 1/4''
- Coolant outlet (4 passes) 1 1/4''
- Receiver volume refrigerant 29,4 dm3
- Max. refrigerant charge 90% at 20°C / 68°F
- R22 32,0 kg
- R134a 32,4 kg
- R407C 30,7 kg
- R404A/R507A 28,3 kg
- Max. pressure 33 bar
- Max. Operating Temperature 120°C
- Max pressure coolant side 10 bar
- Larger outlet connection 35 mm - 1 3/8''