KP98 Danfoss thermostat absorption OIL+60°C/+120°C. 060L113166

  • thermostat is equipped with a single pole to switch contact system.
  • sensor can be mounted warmer or colder than thermostat.
  • Ambient temperature [° C] -40 To 65 ° C
  • Ambient temperature [° F] -40 To 150 ° F
  • Ambient temperature range [° C] -40 To 65 ° C
  • Ambient temperature range [° F] -40 To 150 ° F
  • Approval C U.S. UL, CCC
  • Capillary tube length [in] 39 3/8 in
  • Capillary tube length 1.000 mm
  • Type of Load Adsorption
  • Contact function 2 SPST (NC)
  • Contact rates AC1 = 16 A, 400 V
  • Contact rates AC15 = 10 A, 400 V
  • Contact rates AC3 = 16 A, 400 V
  • Contact rates DC13 = 12 W, 230 V
  • Contact rates LR = 112 A, 400 V
  • Differential Type Adjustable
  • EAN 5702428016490
  • SPF IP30
  • Max.de temperature sensor [° C] 150 ° C
  • Max.de temperature sensor [° F] 302.0 ° F
  • Product Design class B
  • Reset function, left Max
  • Reset function, right Max
  • Size of the probe (Ø x L) [in] 3/8 x 4 1/2 in
  • Probe (Ø x L) [mm] 9.5 x 115 mm
  • Type of probe Remote sensor with capillary tube 
  • Temperature range, left side [° C] 60 to 120 ° C
  • Temperature range, left side [° F] 140 to 250 ° F
  • Temperature range, right side [° C] 100 to 180 ° C
  •    