Assembly of compressors and refrigerating units.

Refrigeration compressors don't just go faulty this has in 98% of all cases a cause. Find out why the compressor is defective.

This can by:

  • low refrigerant which means that the motor winding are not cooled sufficiently.
  • Too many starts in succession , there must be at least 5 minutes between each start and max. 6 per hour
  • too high pressure by failing condenser motor or clogged condenser
  • Old oil from the system mixes with the new , no burn-out filter used to
  • Filter dryer is not replaced at the exchange , too much moisture in the oil.
  • Old mineral oil mixed with synthetic oil mixes in retrofit
  • Liquid is started by a defective expansion valve or over filling of liquid gas.
  • Outside of acceptable conditions of the manufacturer running.
  • Bad vacuum , moister in oil

To claim warranty on a faulty compressor is very difficult.

It must be demonstrated that the replacement/commissioning according to the rules has expired and the compressor has operated under acceptable conditions.

Also to be ensured that the compressor is not on a system is placed where it still remains sour oil was from the old compressor.

  • Always have the filter/dryer be replaced.
  • If the old compressor burnt must be a burn-out filter extra be placed.
  • Care for a company set report with measured pressures and temperatures.

If these conditions are not don well,  a warranty claim by the compressor manufacturers have no chance.