44CC-12.2Y
  • 44CC-12.2Y

44CES-12Y / 44CC-12.2Y Bitzer tandem compressor ECOLINE voor koeltechniek

€ 4.900,00
Exclusief belasting

44CES-12Y / 44CC-12.2Y Bitzer tandem compressor

ECOLINE voor koeltechniek

Gassoort
Voeding
Aantal

DESKUNDIG ADVIES

Professionals in koeltechniek

SINDS 1986

Sinds 1986 in de koudetechniek

FABRIEKSGARANTIE

Altijd orginele fabrieksgarantie

KLANTENSERVICE

+31 413 266 426

44CES-12Y / 44CC-12.2Y Bitzer tandem compressor

ECOLINE voor koeltechniek

 

 

SI

IP

Displacement (1450 RPM 50Hz)

65,0 m3/h

2294.0 CFH

Displacement (1750 RPM 60Hz)

78,4 m3/h

2768.6 CFH

No. of cylinder x bore x stroke

4+4 x 55 mm x 39,3 mm

4+4 2.17 inch x 1.55 inch

Motor voltage (more on request)

380..420V Y/3/50Hz

440..480V Y/3/60Hz

Max operating current

2x15.9A

2x15.9A

Winding ratio

--

--

Starting current (Rotor locked)

2x82.4A Y

2x82.4A Y

Weight

184 kg

406 lb

Maximum pressure (LP/HP)

19 / 28 bar

275 / 403 psi

Connection suction line

35 mm - 1 3/8'

35 mm - 1 3/8'

Connection discharge line

2x22 mm - 7/8'

2x22 mm - 7/8'

Connection cooling water

--

--

Oil type R134a // R407A/C/F // R404A // R507A

tc<55°C: BSE32 / tc>55°C: BSE55 (Option)

tc<130°F: BSE32 / tc>130°F: BSE55 (Option)

Oil type R410A

--

--

Oil type R22 R22 (R12 // R502)

B5.2 (Standard)

B5.2 (Standard)

Oil type R744 (CO2)

--

--

Oil type R290 // R1270

--

--

Oil charge

4,50 dm³

158.4 fl oz

Crankcase heater

2 x 0..120 W PTC (Option)

2 x 0..120 W PTC (Option)

Oil pressure monitoring

--

--

Oil level monitoring

OLC-K1 (Option)

OLC-K1 (Option)

Oil service valve

--

--

Discharge gas temperature sensor

Option

Option

Motor protection

SE-B1

SE-B1

Enclosure class

IP65

IP65

Start unloading

Option

Option

Capacity control

100-75-50-25% (Option)

100-75-50-25% (Option)

Additional fan

Option

Option

Water-cooled cylinder heads

--

--

CIC System

--

--

Vibration dampers

Standard

Standard

Sound power level (+5°C / 50°C)

--

--

Sound power level (-10°C / 45°C)

75,5 dB(A) @ 50Hz

78,0 dB(A) @ 60Hz

Sound power level (-35°C / 40°C)

79,0 dB(A) @ 50Hz

81,5 dB(A) @ 60Hz

Sound pressure level @ 1m (+5°C / 50°C)

--

--

Sound pressure level @ 1m (-10°C / 45°C)

67,5 dB(A) @ 50Hz

70,0 dB(A) @ 60Hz

Sound pressure level @ 1m (-35°C / 40°C)

71,0 dB(A) @ 50Hz

73,5 dB(A) @ 60Hz